MyDro 150, 850

The Next Generation of Wireless Real-Time Alarm, Monitoring, and Remote Control

The MyDro 150 and 850 have all of the functionality of their predecessors, the M110 and M800, with an added onboard interactive display and enhanced electronics. Each remote terminal unit (RTU) includes the necessary hardware for a standard installation—such as a cellular radio, enclosure, backup battery, transformer, and an antenna with a cable and mounting hardware. Purpose-built RTUs simplify and speed installation. There is no programming required, and RTUs are self-enrolling.

View the comparison chart here.

Features:

Reliable Wireless Communications
RTUs feature a game-changing radio with an embedded SIM that supports multiple carriers (AT&T, T-Mobile, and Verizon) as well as a removable SIM for future options such as FirstNet. That means access to multiple carriers is automatic with no need for a site visit to change a SIM. There are no radios to license, nor cellular contracts to set up.

Real-Time Alarms Delivered To All Devices
Real-time alarms are delivered via phone call, text message, email, fax, page, and even to an existing HMI software via an OPC data link. Each alarm is logged with a timestamp for tracking and reporting. The alarm call-out schedule setup is easy, flexible, and intuitive, which allows it to be as simple or sophisticated as users require.

Managed Service—the Complete Package
The Mission system includes cellular data service, data storage, alarm call-outs, reports, and technical support that is on call 24-7-365. The highly reliable, turnkey system offers more features at a lower cost than an in-house setup. No engineering or programming is required and there are no networks to maintain.

View data and reports using the Mission 123SCADA web portal, accessible on any web-enabled device. 123SCADA is the Mission user interface designed with the look and feel of industry-standard HMI SCADA that many new features as well as a legacy user mode. Tabular and graphical reports can be used for compliance reporting and comparative studies. As always, system enhancements are included at no cost and are immediately available.

MyDro 150 RTUs
Real-Time Alarms with Hourly Summaries
The MyDro 150 summarizes analog data, RTU status, pump run times, and pump starts hourly. All alarm data is reported in real-time. Simultaneous pump runtimes can be reported when two pumps run.

MyDro 850 RTUs
Real-Time Alarms and Streaming Data
The MyDro 850 reports pump starts and stops in real-time. Analog values are reported every two minutes or on a 5% change. Volumetric flow calculations can utilize this information along with sump volume (as determined by an analog level sensor or fixed entries) to calculate hourly volumetric flows.

Remote Control
System capabilities may be expanded with optional remote control interfaces, such as automatically controlling offsite wells, tanks, gates, chlorine dosers, variable frequency drives (VFDs), and more, with optional remote control interfaces such as the Tank and Well Control Package, Digital Interconnect, and Analog Interconnect.

Expandable Input/Output
Expand MyDro 850 possibilities with MyDro Expansion Modules. The MyDro supports multiple modules simultaneously. Each type provides the following to onboard capabilities:
• Safe Module Plus—wet well module that adds four pulse channels
• Analog Input—adds seven channels for a total of nine
• Analog Output—adds up to four channels
• Digital Input—adds eight channels for a total of 16
• Digital Relay Output—adds six channels and up to two modules for a total of nine channels

LCD Touch Screen
  • Displays current status
  • Supports local configuration
Radio
  • Cellular radios support LTE, 4G, 3G, and 2G for both GSM (AT&T and partners) and CDMA (Verizon and partners)
  • No radio licenses or site path studies required
Expandable Input/Output
  • Up to 9 analog inputs, 4 analog outputs, 4 pulse inputs, 16 digital inputs, and 9 digital relay outputs all working simultaneously
  • Onboard digital inputs configurable for wire fault supervision or strap on current sensing switch for easier pump run indication
  • RS485 for digital, analog, and pulse expansion via expansion modules
Enhanced
  • 12 or 24 VDC auxiliary output for battery-backed analog instrument loop power
  • Over-the-air upgradable firmware
Links
Download Product Data Sheet

Technical Specifications

MyDro 150 RTU
Data
  • Alarm data: real-time
  • Pump information: pump run times and starts summarized hourly
  • Analog reporting: current value reported hourly
  • Device health: built-in inputs reported hourly
Input/Output
  • Digital inputs: 8 onboard digital inputs (dry) with selectable wire fault supervision, or direct attach current sensing switch (for easiest pump run indication); 3 configurable for pump run summary reporting (number of starts and run time each hour); simultaneous runtimes reported when 2 pumps are monitored
  • Analog inputs: 2 onboard, 4–20 mA isolated or 0–5 VDC; 4 alarm set points each
  • Relay outputs: 3 remotely and locally controllable, form C, dry contact relay outputs, 5 A at 30 VDC, 120 VAC, SPDT, N/O or N/C
  • Analog Outputs: up to 2 available
  • RS485: support for specified expansion modules
  • Pulse inputs: Add 4 with the Safe Module Plus PN OP750
  • Electronic key reader: key reader for site activity tracking and service mode
  • Built-in inputs: AC voltage, battery voltage, board temp, and signal strength; optional second (removal) key reader
Electrical
  • AC power: supervised 120 VAC to 12 VAC, 1.2 A, UL-recognized class II/class III transformer
  • Backup power: 12 V, 5 Ah battery standard, with enhanced charging system—up to 50 hours
  • Auxiliary: auxiliary output selectable 12 VDC or 24 VDC for battery-backed analog instrument loop powering—250 mA max
  • Removable terminals, including: Amphenol PN 20020008-G061B01LF (6 pin for power), 20020004-D081B01LF (D08, D04, D03 for IO)
Other
  • Environment: operating temperature -20—75°C, non-condensing
  • Cellular radio: radios make live, continuous, encrypted TCP socket connections; payload is end-to-end acknowledged; data transmitted through cellular radios that communicate through fourth generation CAT 1 cellular networks.
  • Antenna: omnidirectional antenna with 11' cable, SMA termination, universal mounting bracket
  • Optional SCADA integration OPC link (PN SW586) to client/server HMI
  • Service: requires service packages for the unit and optional expansion boards (see Accessories Catalog for details)
  • Warranty: 1 year manufacturing and material warranty
MyDro 850 RTU
Data
  • Alarm data: real-time
  • Pump information: real-time
  • Analog reporting: every 2 minutes or on 5% change
  • Device health: built-in inputs reported hourly
Input/Output
  • Digital inputs: 8 onboard digital inputs (dry) with selectable wire fault supervision, or direct attach current sensing switch (for easiest pump run indication); expandable to 16 with expansion module PN OP653; up to 8 configurable for pump run; pump states reported in real-time; simultaneous pump runtime reporting supported for up to 7 pumps
  • Analog inputs: 2 onboard, 4–20 mA isolated or 0–5VDC; 4 alarm set points each; expandable to 9 with expansion module PN OP465
  • Relay outputs: 3 remotely controllable, form C, dry contact relay outputs, 5 A at 30VDC, 120VAC, SPDT, N/O or N/C; expandable to 9 with Digital Relay Output expansion module PN OP654
  • RS485: support for specified expansion modules
  • Analog Outputs: up to 4 available with expansion module PN OP461
  • Pulse inputs: Add 4 with the Safe Module Plus PN OP750
  • Electronic key reader: key reader for site activity tracking and service mode
  • Built-in inputs: AC voltage, battery voltage, board temp, and signal strength; optional second (removal) key reader
Electrical
  • AC power: supervised 120 VAC to 12 VAC, 1.2 A, UL-recognized class II/class III transformer
  • Backup power: 12 V, 5 Ah battery standard, with enhanced charging system—up to 18 hours
  • Auxiliary: auxiliary output selectable 12VDC or 24VDC for battery-backed analog instrument loop powering—250 mA max
  • Removable terminals, including: Amphenol PN 20020008-G061B01LF (6 pin for power,) 20020004-D081B01LF (D08, D04, D03 for IO)
Other
  • Environment: operating temperature -20—75°C, non-condensing
  • Cellular radio: radios make live, continuous, encrypted TCP socket connections; payload is end-to-end acknowledged; data transmitted through cellular radios that communicate through fourth generation CAT 1 cellular networks.
  • Antenna: omnidirectional antenna with 11' cable, SMA termination, universal mounting bracket
  • Optional SCADA Integration OPC Link (PN SW586) to client/server HMI
  • Automated remote control package — Tank and Well (see Accessories Catalog for more details)
  • Service: requires service packages for the unit and optional expansion boards (see Accessories Catalog for details)
  • Warranty: 1 year manufacturing and material warranty

You’re Never Alone

You will receive experienced technical support, including access to the people that built the system if needed. This includes comprehensive training, regular webinars, live support during business hours and after-hours support that is always available on a responsive callback basis for emergencies—at no extra charge.